Table 16 — Alarm and Alert Codes (cont)

DISPLAY

ALARM

DESCRIPTION

ACTION TAKEN

CIRCUIT

RESET

PROBABLE CAUSE

OR

ALERT

BY CONTROL

PUMPDOWN

METHOD

63

Alarm

Complete unit shutdown

Alarm only

Auto.

Check individual alarms

64

Alert

Loss of charge, circuit A

Circuit cannot start

Auto.

Refrigerant leak or transducer
failure

65

Loss of charge, circuit B

Circuit cannot start

Auto.

66

Alarm

FSM communication loss

FSM forces removed

Auto.

Wiring faulty or module failure

67

Alarm

Transducer calibration date code failure

Unit cannot start

Auto.

Incorrect date code entered

68,69

Not used

70

Alert

High leaving chilled fluid temperature

Alarm only

Auto.

Building load greater than unit capacity,
low water/brine flow, or compressor
fault. Check for other alarms or alerts.

LEGEND

CPCS — Compressor Protection Control Module
FSM

Flotronic™ System Manager

PS

Power Supply

WSM

Water System Manager

*Reset automatic first time, manual if repeated same day.

Possible causes of failure:
1. High-Pressure Switch Open — High-pressure switch for

each compressor is wired in series with 24-v power that
energizes compressor control relay. If high-pressure switch
opens during operation, compressor stops. This is
detected by microprocessor through the feedback
terminals.

2. DSIO-LV or DSIO-EXV Module Failure — If a DSIO-LV

relay module relay fails open or closed, microprocessor
detects this, locks compressor off, and indicates an
error.

3. Wiring Errors — If a wiring error exists causing CPCS,

CR, or feedback switch to not function properly, micro-
processor indicates an error.

4. Processor (PSIO) Failure — If hardware that monitors

feedback switch fails, or processor fails to energize relay
module relay to on, an error may be indicated.
NOTE: The control does not detect circuit breaker fail-
ures. If a circuit breaker trips on lead compressor in a
circuit, a low oil pressure failure is indicated. On the other
compressors, no failure is indicated.

5. Ground Fault Module on 130-210 and associated modu-

lar units (CGFA or CGFB) Open — Module contacts are
in lead compressor circuits, but ground fault could be in
any compressor in affected circuit.
Ground fault of any 040-110 and associated modular unit
compressor (field-supplied accessory on 040-060 and 070,
60 Hz units; standard on 070, 50 Hz and 80-110 and as-
sociated modular units) will cause a trip.

6. Checkout Procedure — Shut off main power to unit. Turn

on

control

power,

then

step

through

subfunc-

tion

to proper compressor number (i.e., failure

code 5 is compressor B1). Next, energize the step. If step
works correctly, then failure code is caused by:
• HPS (high-pressure switch) open
• Misplaced feedback wire from J4 and J5 terminals
• Ground wire and 24-v feeds reversed on one or more

points on J3

Compressor Alarm/Alert Circuit —

For compres-

sor A1 circuit, processor closes contacts between J4 termi-
nals 2 and 3 to start compressor. See Fig. 11A-11C. Safeties
shown to left of J4 must be closed in order for power to
reach compressor control relay, and the feedback input ter-
minals on J3.

Failure of power to terminal 1 on J3, when contacts be-

tween 2 and 3 on J4 should be closed, causes a code 1 alert.

Terminal 2 on J3 is the other leg of the compressor A1

feedback channel. It is connected to the 24-v common.
NOTE: Similar connections for each compressor can be fol-
lowed on the unit wiring diagrams located on the unit.
Code 9

Leaving fluid thermistor failure (alarm)

Code 10

Entering fluid thermistor failure (alarm)

If temperature measured by these thermistors is outside

range of –40 to 240 F (–40 to 116 C), unit shuts down after
going through a normal pumpout. Reset is automatic if tem-
perature returns to the acceptable range, and unit start-up fol-
lows normal sequence. The cause of the fault is usually a
bad thermistor, wiring error, or loose connection.
Code 19

Compressor A1 suction sensor failure (alert)

Code 20

Compressor B1 suction sensor failure (alert)

On units with thermistors, if temperature measured by these

thermistors is outside the range of –40 to 240 F (–40 to
116 C), affected circuit shuts down after going through a nor-
mal pumpout. Other circuit continues to run. Reset is auto-
matic if temperature returns to the acceptable range, and cir-
cuit start-up follows normal sequence. The cause of this fault
is usually a bad thermistor, wiring error, or loose
connection.

On units with transducers, if the saturated suction tem-

perature is greater than the leaving fluid temperature plus
10° F (5.5 C) for more than 5 minutes, the affected circuit
shuts down (after going through normal pumpout). The reset
is automatic if the saturated suction temperature returns to
the acceptable range and start-up follows the normal se-
quence. The cause of this fault is usually a bad transducer,
a wiring error, or a loose connection.