Adjus t menu – tekmar 422 Universal Reset Module User Manual

Page 8

background image

© 2007

D 422 - 08/07

8 of 32

Item Field

Range

Access

Description

-60 to 45°F

(-51.0 to 7.0°C)

Default = 10°F

(-12.0°C)

InS

Ad

OUTDOOR DESIGN

SECTION B

The design outdoor air temperature used in the heat
loss calculations for the heating system. Typically set
to the temperature of the coldest day of the year.

VAr, FLt

Default = VAr

InS

Ad

MIX 1 MODE

SECTION G

Select the type of mixing device to be used for Mix 1.
Options are variable speed injection pump (VAr) or
floating action (FLt).

1 HRF1
2 HRF2
3 Fancoil
4 Fin-tube Convector
5 Radiator
6 Baseboard
Default = 1

InS

Ad

MIX 1 TERMINAL

SECTION B

The type of heating terminal units that are being
used in Mix 1 zones.

40 to 100°F

(4.5 to 38.0°C)

Default = 70°F (21.0°C)

Ad

MIX 1 INDOOR

SECTION B

The design indoor air temperature used in the heat
loss calculation for Mix 1 zones. Typically set to
70°F (21.0°C).

70 to 220°F

(21.0 to 104.5°C)

Default = 120°F

(49.0°C)

InS

Ad

MIX 1 DESIGN

SECTION B

The supply water temperature required for the Mix 1
zones on the typical coldest day of the year.

OFF, 40 to 150°F

(OFF, 4.5 to 65.5°C)

Default = OFF

Ad

MIX 1 MINIMUM

SECTION G

The minimum allowed Mix 1 target temperature.

80 to 220°F, OFF

(26.5 to 104.5°C, OFF)

Default = 140°F

(60.0°C)

Ad

MIX 1 MAXIMUM

SECTION G

The maximum allowed Mix 1 target temperature.

Adjust Menu (1 of 5)

The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.

Continued on next page.