View menu – tekmar 422 Universal Reset Module User Manual
Page 7
7 of 32
© 2007
D 422 - 08/07
Item Field
Range
Access
Description
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Ad
BOILER TARGET
SECTION C
The boiler target is the temperature the control is currently
trying to maintain at the boiler supply sensor. “– – –” is
displayed when no heat is required for boiler zones.
Note:
This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
BOILER RETURN
SECTION G
Current boiler return water temperature as measured
by the boiler sensor.
Note:
This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Ret.
0-100%
Ad
BOILER MODULATION
SECTION C
Current percent modulation of the boiler’s burner.
Note:
This item is only available when the Boiler
On-Off / Mod DIP switch is set to Mod, and the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
0 to 9999 hr
InS
Ad
BOILER
The total running time of the boiler since this item
was last cleared. To clear this item, press the Up
and Down buttons simultaneously while viewing
this item.
Note:
This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
View Menu (2 of 2)
After the last item, the control returns to the first item in the menu.
VIEW MENU