Boiler Outdoor Reset

There is a water temperature and therefore a characterized
heating curve for each communication bus. When using
boiler temperature water to heat zones, the installer will
be required to set a boiler characterized heating curve.
This requires the tN4 DIP switch to be set to Boiler and
the Boiler Sensor DIP switch set to Supply.

Boiler Terminal Unit Defaults
When a terminal unit is selected for boiler zones, the
control loads default values for the boiler design, boiler
maximum supply, and boiler minimum supply temperatures.
The factory defaults can be changed to better match the
installed system. Locate the Boiler Terminal Unit setting
in the Adjust menu.

Mix 1 and Mix 2 Outdoor Reset

Each tN4 communication bus operates on a separate water
temperature. Therefore a separate characterized heating
curve is required for Mix 1 and, if the tN4 DIP switch is
selected to Mix 2, for mix 2 as well.

Mix 1 and 2 Terminal Unit Defaults
When a terminal unit is selected for Mix 1 (or Mix 2),
the control loads default values for the mix design, mix
maximum supply, and mix minimum supply temperatures.
The factory defaults can be changed to better match the
installed system.

• Locate the Mix 1 and Mix 2 terminal unit settings in the

Adjust menu.

Mix Characterized Heating Curve

Terminal Unit

Mix

Design

Outdoor

Design

Mix

Indoor

Decreasing Outdoor Temperatures

Increasing Mix T

e

mper

ature

Terminal Unit

BOIL DSGN

BOIL MAX

BOIL MIN

High Mass Radiant (1)

120°F (49°C)

140°F (60°C)

OFF

Low Mass Radiant (2)

140°F (60°C)

160°F (71°C)

OFF

Fancoil (3)

190°F (88°C)

210°F (99°C)

140°F (60°C)

Fin-Tube Convector (4)

180°F (82°C)

200°F (93°C)

140°F (60°C)

Radiator (5)

160°F (71°C)

180°F (82°C)

140°F (60°C)

Baseboard (6)

150°F (76°C)

170°F (77°C)

140°F (60°C)

Boiler Indoor Design
The boiler indoor design temperature is the indoor temperature
the heating designer chose while calculating the heat loss for
the boiler water heated zones. This temperature is typically
70°F (21.0°C). This setting establishes the beginning of
the boiler characterized heating curve.

• Locate the Boiler Indoor Design setting in the Adjust

menu.

Boiler Design Temperature
The boiler design supply temperature is the boiler water
temperature required to heat the zones on the typical
coldest day of the year.

• Locate the Boiler Design setting in the Adjust menu.

Terminal Unit

MIX DSGN

MIX MAX

MIX MIN

High Mass Radiant (1)

120°F (49°C)

140°F (60°C)

OFF

Low Mass Radiant (2)

140°F (60°C)

160°F (71°C)

OFF

Fancoil (3)

190°F (88°C)

210°F (99°C)

100°F (38°C)

Fin-Tube Convector (4)

180°F (82°C)

200°F (93°C)

OFF

Radiator (5)

160°F (71°C)

180°F (82°C)

OFF

Baseboard (6)

150°F (76°C)

170°F (77°C)

OFF

Mix 1 and Mix 2 Indoor Design
The Mix 1 (or Mix 2) indoor design temperature is the indoor
temperature the heating designer picked while calculating
the heat loss for the building for the Mix 1 (or Mix 2) water
heated zones. This temperature is typically 70°F (21.0°C).
This setting establishes the beginning of the Mix 1 (or Mix 2)
characterized heating curve.

• Locate the Mix 1 and Mix 2 Indoor Design settings in

the Adjust menu.

Mix 1 and Mix 2 Design Temperature
The Mix 1 (or Mix 2) design supply temperature is the mix
supply water temperature required to heat the zones when
the outdoor temperature is as cold as the outdoor design
temperature.

• Locate the Mix 1 and Mix 2 Design settings in the Adjust

menu.

Boiler Characterized Heating Curve

Terminal Unit

Boiler

Design

Boiler

Indoor

Outdoor

Design

Decreasing Outdoor Temperatures

Increasing W

a

ter T

e

mperatures