Troubleshooting – tekmar 422 Universal Reset Module User Manual
Page 31

31 of 32
© 2007
D 422 - 08/07
Symptom
Possible Causes
Corrective Action
Boiler does not fire 
when there is a DHW 
or Setpoint Demand
No voltage present on demand 
terminals.
Test voltage across demand terminals using 
voltmeter.
Control in Unoccupied and DHW 
Unoccupied or Setpoint Unoccupied set 
to OFF.
Check which schedule the 422 is operating on.
Boiler contact is not connected to boiler 
thermostat connection.
Trace wires from boiler contact to boiler thermostat 
connection. Use the Test sequence to check the 
boiler contact.
Mixing valve will not 
open.
No voltage present on actuator motor.
Mix 1 Mode setting must be set to FLt.
Boiler Return Protection.
Mixing valve will not open until the boiler supply 
temperature exceeds the boiler minimum setting.
Actuator rotating in wrong direction to 
open valve
Reverse open and close wires on actuator.
Variable speed 
injection pump does 
not operate.
No current present on variable speed 
injection pump.
Mix 1 Mode setting must be set to VAr.
Boiler Return Protection.
Variable speed injection pump will not operate until 
the boiler supply temperature exceeds the boiler 
minimum setting.
A non-wet rotor pump has been installed.
Variable speed injection will only operate with wet 
rotor pumps. Read E 021 and check pump type.
Fuse is blown.
Determine if pump is jammed or seized. Replace 
fuse. 
Display is not on.
No voltage to control.
Check breaker panel or disconnect. Check voltage 
using a voltmeter.
Plugs are not connected between the 
422 to the Zone Manager.
Ensure the plugs are secured to the Zone 
Manager pins.
Fuse is blown.
Check fuse on Zone Manager. Check total 
VA draw on all thermostats and zone valves 
connected to the Zone Manager. This cannot 
exceed 40 VA.
Troubleshooting
Error Message
Description
BOILER BUS AND RETURN SENSOR CONFLICT
There is a DIP switch settings conflict. The Boiler DIP switch is set to Ret and the tN4 bus DIP 
switch is set to Boiler. Once the Boiler DIP switch is set to Sup or the tN4 bus DIP switch is set 
to Mix 2, the error message clears.
tekmar STAGER SETTING CONFLICT
There is a DIP switch settings conflict. The tekmar Stager DIP switch is set to On and the Boiler 
Sensor DIP switch is set to Ret. Once the Boiler Sensor DIP switch is set to Sup or the tekmar 
Stager DIP switch is set to Off, the error message clears.
DEVICE ERROR AT ADDRESS #:##
#:## is the address of the device with the error. The bus number displays before the colon, 
and the device number displays after. Go to the device with the address displayed.
Possible Addresses:
b:01 to b:24 - Device Error on Boiler Bus
1:01 to 1:24 - Device Error on Bus 1
2:01 to 2:24 - Device Error on Bus 2
Error Messages (3 of 3)
