tekmar 422 Universal Reset Module User Manual
Page 26

© 2007
D 422 - 08/07
26 of 32
Boiler Target During Setpoint
The boiler target temperature during a Setpoint Demand is 
increased to at least the Setpoint setting. This temperature is 
maintained as long as the control has a setpoint demand.
Setpoint During UnOccupied
The control has a Setpoint UnOccupied setting that allows 
the installer to select On or Off. When set to On, and the 
control receives a Setpoint Demand during an UnOccupied or 
Sleep period, the control continues operation of the Setpoint 
system as it would during Occupied and Wake periods. When 
set to Off, the control can ignore a Setpoint Demand for the 
duration of the UnOccupied and Sleep periods.
Setpoint Modes
The Setpoint Mode determines the operation of the primary pump. 
The Setpoint Mode setting is found in the Adjust menu.
Setpoint Mode 1 - Setpoint in Parallel
Whenever a setpoint demand is present, the boiler is 
operated to maintain the setpoint target. The primary pump 
(P1) does not turn on, but may operate based on either a 
Boiler, Mixing or a DHW Demand.
It is assumed that the Setpoint pump will provide adequate 
flow through the heat exchanger and the boiler.
Setpoint Mode 3 – Setpoint in Primary / Secondary
Whenever a setpoint demand is present, the primary pump 
(P1) is turned on and the boiler is operated to maintain the 
setpoint target.
Setpoint Mode 2 - Setpoint in Parallel with Priority
When a Setpoint Demand is present, the boiler is operated 
to maintain the setpoint target. The primary pump (P1) can 
operate when a boiler demand is present. If the boiler is 
unable to maintain the boiler target temperature, space heating 
zones are shut off sequentially using tN4 communication in 
order to provide priority for the setpoint load. This is known 
as zone load shedding.
It is assumed that the setpoint pump will provide adequate 
flow through the heat exchanger and the boiler.
Setpoint Mode 4 - Setpoint in Primary / Secondary 
with Priority
Whenever a Setpoint Demand is present, the primary pump 
(P1) is turned on and the boiler is operated to maintain the 
setpoint target. Space heating zones will be shut off using 
zone load shedding if the boiler is unable to maintain the 
boiler target temperature.
Setpoint Priority Override
Setpoint Priority Override applies to SETPOINT MODE 
2 and MODE 4. To prevent the building from cooling off 
too much or the possibility of a potential freeze up during 
setpoint priority, the control limits the amount of time for 
setpoint priority. As the outdoor air temperature becomes 
colder, the length of time the control provides setpoint 
priority is reduced. Once the allowed time for priority has 
elapsed, the control overrides the setpoint priority and 
resumes space heating.
Conditional Setpoint Priority
If the boiler supply temperature is maintained at or above 
the required temperature during setpoint generation, this 
indicates that the boiler has enough capacity for setpoint 
and possibly heating as well. As long as the boiler target 
temperature is maintained, setpoint and heating occur at 
the same time.
Primary
Pump
Setpoint
Mode = 3
Setpoint
Primary
Pump
OFF
Mode = 4
Primary
Pump
Setpoint
Mode = 1
Setpoint
Primary
Pump
OFF
Mode = 2
