Adjus t menu – tekmar 422 Universal Reset Module User Manual

Page 12

background image

© 2007

D 422 - 08/07

12 of 32

ADJUS

T MENU

Item Field

Range

Access

Description

60 to 220°F

(15.5 to 104.5°C)

Default = 180°F

(82.0°C)

Ad

SETPOINT OCCUPIED

SECTION J

The minimum boiler target temperature when a
setpoint demand is present during the Wake and
Occupied periods.

Note:

This item is only available when Setpoint Mode

is set 1 through 4.

OFF, ON

Default = OFF

Ad

SETPOINT UNOCCUPIED

SECTION J

Selects whether or not a Setpoint demand will be
responded to during the Sleep and Unoccupied
periods.

Note:

This item is only available when Setpoint Mode

is set 1 through 4 and a network setback schedule
is selected.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 70°F (21.0°C)

InS

Ad

WWSD OCCUPIED

SECTION B

The system’s warm weather shut down temperature
during the Wake and Occupied periods.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 60°F (15.5°C)

Ad

WWSD UNOCCUPIED

SECTION B

The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.

Note:

This item is only available when the Schedule

is not set to OFF.

Adjust Menu (5 of 5)

After the last item, the control returns to the first item in the menu.