Adjus t menu – tekmar 422 Universal Reset Module User Manual
Page 12
© 2007
D 422 - 08/07
12 of 32
ADJUS
T MENU
Item Field
Range
Access
Description
60 to 220°F
(15.5 to 104.5°C)
Default = 180°F
(82.0°C)
Ad
SETPOINT OCCUPIED
SECTION J
The minimum boiler target temperature when a
setpoint demand is present during the Wake and
Occupied periods.
Note:
This item is only available when Setpoint Mode
is set 1 through 4.
OFF, ON
Default = OFF
Ad
SETPOINT UNOCCUPIED
SECTION J
Selects whether or not a Setpoint demand will be
responded to during the Sleep and Unoccupied
periods.
Note:
This item is only available when Setpoint Mode
is set 1 through 4 and a network setback schedule
is selected.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 70°F (21.0°C)
InS
Ad
WWSD OCCUPIED
SECTION B
The system’s warm weather shut down temperature
during the Wake and Occupied periods.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 60°F (15.5°C)
Ad
WWSD UNOCCUPIED
SECTION B
The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.
Note:
This item is only available when the Schedule
is not set to OFF.
Adjust Menu (5 of 5)
After the last item, the control returns to the first item in the menu.