Item Field

Range

Access

Description

40 to 100°F

(4.5 to 38.0°C)

Default = 70°F

(21.0°C)

Ad

BOILER INDOOR

SECTION B

The design indoor air temperature used in the heat
loss calculation for the boiler zones. Typically set to
70°F (21.0°C).

Note:

This item is only available when the Boiler

Sensor Sup / Ret DIP switch is set to Sup and the
tN4 DIP switch is set to Boiler.

70 to 220°F

(21.0 to 104.5°C)

Default = 180°F

(82.0°C)

InS

Ad

BOILER DESIGN

SECTION B

The supply water temperature required for boiler
zones on the typical coldest day of the year.

Note:

This item is only available when the Boiler

Sensor Sup / Ret DIP switch is set to Sup and the
tN4 DIP switch is set to Boiler.

OFF, 80 to 180°F

(OFF, 26.5 to 82.0°C)

Default = 140°F

(60.0°C)

InS

Ad

BOILER MINIMUM

SECTION C

The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommend supply water
temperatures.

120 to 225°F, OFF

(49.0 to 107.0°C, OFF)

Default = 200°F

(93.5°C)

Ad

BOILER MAXIMUM

SECTION C

The maximum allowed boiler target temperature.

Note:

This item is only available when the Boiler

Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.

0:00 to 3:00 min

Default = 0:10 min

Ad

FIRE DELAY

SECTION C

The time delay the control can expect between the
time that the relay contact closes to fire the boiler
and when the burner actually fires.

Note:

This item is only available when the Boiler

Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.

Au, 2 to 42°F

(Au, 1 to 23.5°C)

Default = Au

Ad

BOILER DIFFERENTIAL

SECTION C

The temperature differential that the control is to use
when it is operating the boiler.

Note:

This item is only available when the Boiler

Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.

10 to 230 seconds

Default = 30 seconds

Ad

BOILER MOTOR

SECTION C

The amount of time required for the modulating
actuating motor to fully open the gas valve or operate
the fan speed from a stopped position to full speed
on a modulating boiler.
Note:

This item is only available when the Boiler

Sensor Sup / Ret DIP switch is set to Sup, the Boiler
On-Off / Mod DIP switch is set to Mod and the tekmar
stager DIP switch is set to OFF.

Adjust Menu (3 of 5)

Continued on next page.

ADJUS

T MENU