Sequence of operation, Tekmarnet – tekmar 422 Universal Reset Module User Manual
Page 16

© 2007
D 422 - 08/07
16 of 32
tekmarNet
®
4 Communication
Section A
tekmarNet
®
4 (tN4) communicates between tN4 devices
(thermostats, Reset Module and Expansion Modules). 
Each tN4 device is connected to a tN4 communication 
bus using two wires. Each tN4 bus adjusts a single water 
temperature in the system using indoor temperature 
feedback. The Universal Reset Module 422 allows for two 
tN4 buses. This allows you to control a system with two 
separate water temperatures.
A system that has more than one tN4 bus is referred to as 
a tN4 network.
Outdoor Reset Module
The Universal Reset Module 422 is the system control 
for a hydronic heating system. The 422 operates a single 
heat source such as a boiler, one or two mixing devices, 
a domestic hot water tank, and responds to other heating 
requirements such as pool heating and snow melting. The 
422 also coordinates and optimizes the operation of all the 
tN4 thermostats.
tN4 Thermostat
The tN4 thermostat operates heating, cooling, and or 
ventilation equipment for a zone. Several tN4 thermostats 
may work in a group when operating a cooling system. Up 
to 24 tN4 thermostats can connect to a single tN4 bus.
Outdoor Reset
Section B
In a heating system, the rate of heat supplied to the building 
must equal the rate of which heat is lost. If the two rates are 
not equal, the building will either cool off or over heat.
The rate of building heat loss depends mostly on the outdoor 
temperature. Outdoor Reset allows a hot water heating 
system to increase the water temperature, adding heat to 
the building, as the outdoor temperature drops. The rate 
at which the water temperature is changed is defined by 
the characterized heating curve.
Characterized Heating Curves
A characterized heating curve determines the amount the 
supply water temperature is raised for every 1° drop in 
outdoor air temperature. There is a characterized heating 
curve for each tN4 communication bus.
The characterized heating curve takes into account the 
type of terminal unit that the system is using. Since different 
types of heating terminal units transfer heat to a space using 
different proportions of radiation, convection and conduction, 
the supply water temperature must be controlled differently. 
Each tN4 bus is assigned a terminal unit setting that the 
control uses to vary the supply water temperature to suit 
to the terminal unit used. This improves the control of the 
air temperature in the building.
Indoor Temperature Feedback
Most buildings have internal heat gains due to people, 
passive solar heating and mechanical or electrical equipment. 
Likewise, wind loads cause a building to lose heat faster than 
during design conditions. If only the outdoor temperature is 
measured, the control cannot compensate for these internal 
heat gains or loses and the building may over or under heat. 
In order to maintain the most comfortable temperature, 
the control uses indoor temperature feedback from tN4 
thermostats in order to adjust the water temperature on 
each tN4 bus on a continual basis.
Sequence of Operation
Zone A1
Zone A2
Power
Zone Group Pump A
Zone A3
Zone B1
Zone B2
Zone B3
tN4
Zone Group Pump B
Bus 1
Bus 2
Network
tekmarNet
®
4
Thermostats
tekmarNet
®
4
Thermostats
tN4
H7008B
Test
Item
Menu
/
Do not apply power
