tekmar 422 Universal Reset Module User Manual
Page 17

17 of 32
© 2007
D 422 - 08/07
Terminal Unit
There is a terminal unit setting for each tN4 bus. The 
Terminal Unit setting is found in the Adjust menu.
Hydronic Radiant Floor (1)
Terminal type 1 is a heavy, or high mass, hydronic radiant floor 
system. This type of a hydronic radiant floor is embedded in 
either a thick concrete or gypsum pour. This heating system 
has a large thermal mass and is slow acting.
Hydronic Radiant Floor (2)
Terminal type 2 is a light, or low mass, hydronic radiant 
floor system. Most commonly, this type of radiant heating 
system is either attached to the bottom of a wood sub floor, 
suspended in the joist space, or sandwiched between the 
subfloor and the surface. This type of radiant system has 
a relatively low thermal mass and responds faster than a 
high mass system.
Fancoil (3)
Terminal type 3 is a fancoil terminal unit or air handling 
unit (AHU) consisting of a hydronic heating coil and either 
a fan or blower. Air is forced across the coil at a constant 
velocity by the fan or blower and is then delivered into the 
building space.
Fin–tube Convector (4)
Terminal type 4 is a convector terminal unit is made up of 
a heating element with fins on it. This type of terminal unit 
relies on the natural convection of air across the heating 
element to deliver heated air into the space. The amount 
of natural convection is dependant on the supply water 
temperature to the heating element and the room air 
temperature.
Radiator (5)
Terminal type 5 is a radiator terminal unit has a large heated 
surface that is exposed to the room. A radiator provides 
heat to the room through radiant heat transfer and natural 
convection.
Baseboard (6)
Terminal type 6 is a baseboard terminal unit is similar to a 
radiator, but has a low profile and is installed at the base 
of the wall. The proportion of heat transferred by radiation 
from a baseboard is greater than that from a fin-tube 
convector.
Outdoor Design Temperature
The outdoor design temperature is typically the coldest 
outdoor air temperature of the year. This temperature is 
used when doing the heat loss calculations for the building 
and is used to size the heating system equipment. If a cold 
outdoor design temperature is selected, the supply water 
temperature rises gradually as the outdoor temperature 
drops. If a warm outdoor design temperature is selected, 
the supply water temperature rises rapidly as the outdoor 
temperature drops.
The outdoor design setting is found in the Adjust menu.
Warm Weather Shut Down (WWSD)
The Warm Weather Shut Down is the outdoor temperature 
at which hydronic heating is no longer required. The control 
closes mixing valves and variable speed pumps are not 
operated. The boiler operates only when a Domestic Hot 
Water (DHW) Demand or a Setpoint Demand is present.
The WWSD setting is found in the Adjust menu.
