View menu display menus – tekmar 422 Universal Reset Module User Manual
Page 6
© 2007
D 422 - 08/07
6 of 32
View Menu (1 of 2)
Item Field
Range
Access
Description
-76 to 149°F
(-60.0 to 65.0°C)
InS
Ad
OUTDOOR
SECTION B
Current outdoor air temperature as measured by the
outdoor sensor.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
MIX 1 SUPPLY
SECTION B
Current Mix 1 supply water temperature as measured
by the Mix 1 supply sensor.
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Ad
MIX 1 TARGET
SECTION C
The Mix 1 target is the temperature the control
is currently trying to maintain at the Mix 1 supply
sensor. “– – –” is displayed when no heat is required
for Mix 1 zones.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
MIX 2 SUPPLY
SECTION B
Current Mix 2 supply water temperature as measured
by the Mix 2 supply sensor.
Note:
This item is only available when the tN4 DIP
switch is set to Mix 2.
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Ad
MIX 2 TARGET
SECTION C
The mix 2 target is the temperature the control
is currently trying to maintain at the Mix 2 supply
sensor. “– – –” is displayed when no heat is required
for mix 2 zones.
Note:
This item is only available when the tN4 DIP
switch is set to Mix 2.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
BOILER SUPPLY
SECTION C
Current boiler supply water temperature as measured
by the boiler sensor.
Note:
This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
The View menu items display the current operating
temperatures and status information of the system.
Continued on next page.
VIEW MENU
Display Menus