View menu (1 of 1), Display description range – tekmar 263 Boiler Control User Manual
Page 26

© 2009 D 263 - 03/09
26 of 36
View Menu (1 of 1)
Outdoor Current outdoor air temperature as measured by the
outdoor sensor.
-76 to 149°F
(-60 to 65°C)
Room Occupied Current room air temperature as measured by the
indoor sensor.
This item is only available when an indoor sensor is connected to
the control.
23 to 113°F
(-5 to 45°C)
Boiler Supply Current boiler supply water temperature as measured
by the boiler supply sensor.
-22 to 266°F
(-30 to 130°C)
Boiler Target Boiler target temperature is the temperature the
control is currently trying to maintain at the boiler supply sensor
+/- ½ of the differential.
– – –, 35 to 230°F
(– – –, 2 to 110°C)
DHW Current DHW tank temperature as measured by the DHW
sensor.
A DHW sensor must be installed to view this item.
– – –, 35 to 230°F
(– – –, 2 to 110°C
B3
Boiler Modulation Current percent modulation of the boiler’s burner.
This item is only available in operating mode 2.
0 to 100%
Boiler Hours The total running time of the boiler since this item
was last cleared. To clear this item, press the
▲ and ▼ button
simultaneously while viewing this item.
This item is only available in operating mode 2.
0 to 1999 hr
Boiler 1 Hours The total running time of boiler 1 since this item
was last cleared. To clear this item, press the
▲ and ▼ button
simultaneously while viewing this item.
This item is only available in operating mode 1 and boiler 1 is set to
Au (automatic).
0 to 1999 hr
Boiler 2 Hours The total running time of boiler 2 since this item
was last cleared. To clear this item, press the
▲ and ▼ button
simultaneously while viewing this item.
This item is only available in operating mode 1 and boiler 2 is set to
Au (automatic).
0 to 1999 hr
Display
Description
Range
Section
Installer