View Menu (1 of 1)

Outdoor Current outdoor air temperature as measured by the
outdoor sensor.

-76 to 149°F
(-60 to 65°C)

Room Occupied Current room air temperature as measured by the
indoor sensor.
This item is only available when an indoor sensor is connected to
the control.

23 to 113°F
(-5 to 45°C)

Boiler Supply Current boiler supply water temperature as measured
by the boiler supply sensor.

-22 to 266°F
(-30 to 130°C)

Boiler Target Boiler target temperature is the temperature the
control is currently trying to maintain at the boiler supply sensor
+/- ½ of the differential.

– – –, 35 to 230°F
(– – –, 2 to 110°C)

DHW Current DHW tank temperature as measured by the DHW
sensor.
A DHW sensor must be installed to view this item.

– – –, 35 to 230°F
(– – –, 2 to 110°C

B3

Boiler Modulation Current percent modulation of the boiler’s burner.
This item is only available in operating mode 2.

0 to 100%

Boiler Hours The total running time of the boiler since this item
was last cleared. To clear this item, press the

▲ and ▼ button

simultaneously while viewing this item.
This item is only available in operating mode 2.

0 to 1999 hr

Boiler 1 Hours The total running time of boiler 1 since this item
was last cleared. To clear this item, press the

▲ and ▼ button

simultaneously while viewing this item.
This item is only available in operating mode 1 and boiler 1 is set to
Au (automatic).

0 to 1999 hr

Boiler 2 Hours The total running time of boiler 2 since this item
was last cleared. To clear this item, press the

▲ and ▼ button

simultaneously while viewing this item.
This item is only available in operating mode 1 and boiler 2 is set to
Au (automatic).

0 to 1999 hr

Display

Description

Range

Section

Installer

Ad

vanced