DHW MODE AND PRIORITY OPERATION

The control has four different modes of DHW operation, which depends on the piping arrangement of the DHW tank. It is often
desirable to limit or even stop the flow of heat to the heating system when the DHW tank calls for heat. This allows for a faster
recovery of the DHW tank.

DHW Mode 1 - DHW in Parallel no Priority

When a DHW Demand is present, the DHW Pmp / Vlv contact
(terminals 9 and 10) closes. The primary pump contact does not turn
on, but may operate based on a boiler demand.

It is assumed that the DHW pump will provide adequate flow
through the heat exchanger and the boiler.

DHW Mode 2 - DHW in Parallel with Priority

When a DHW Demand is present, the DHW Pmp / Vlv contact
(terminals 9 and 10) closes and the primary pump contact is opened.

It is assumed that the DHW pump will provide adequate flow
through the heat exchanger and the boiler.

DHW Mode 3 - DHW in Primary / Secondary no Priority

When a DHW Demand is present, the DHW Pmp / Vlv contact
(terminals 9 and 10) is closed and the primary pump contact is closed.

This mode can be used if a DHW tank is piped in direct return and
a DHW valve is installed.

DHW Mode 4 - DHW in Primary / Secondary with Priority

When a DHW Demand is present, the DHW Pmp / Vlv contact (terminals 9 and 10) is closed and the primary pump contact is
closed. Priority can only be obtained using external wiring. During a priority override, the DHW Pmp / Vlv contact is opened until
the heating system has recovered before returning to DHW operation.

This mode can be used if a DHW tank is piped in direct return and a DHW valve is installed.

DHW MODE 4
External Priority

Interlock

Power to External

Boiler Zones

N.C.

L

DHW

Pump

N

N.O.

L

N

COIL

Power from

DHW Pump / Vlv

Contact

DHW PRIORITY OVERRIDE

The DHW Priority Override applies to DHW modes 2 and 4. To prevent
the building from cooling off too much or the possibility of a potential
freeze up during DHW priority, the control limits the amount of time
for DHW priority. As the outdoor air temperature becomes colder, the
length of time that the control provides DHW priority is reduced. Once
the allowed time for priority has elapsed, the control overrides the DHW
priority and resumes space heating.

To provide external DHW priority, the space heating zones must be
interlocked with the DHW Pmp / Vlv contact. During demands, the
DHW Pmp / Vlv

contact must remove any power to all space heating

zone valves or zone pumps.

DHW

Pump

Primary

Pump

Boiler

Pump

DHW

Pump

Primary

Pump

Boiler

Pump

DHW

Pump

Primary

Pump

Boiler

Pump

DHW

Pump

Primary

Pump

Boiler

Pump

Disable

Using External

Wiring

Increasing Air Temperature

Incr

easing Time

DHW priorit

y demand time limit

Outdoor Air Temperature

DHW Priority Override

DHW Priority Override