Page 20: Modulation output

background image

© 2009 D 263 - 03/09

20 of 36

Relay 1 Contact

Mode 1 - Two ON / OFF Stages

The Relay 1 terminals (11 and 12) are isolated outputs in the control. There is no
power available on these terminals from the control. These terminals are to be used
as a switch to either make or break power to a boiler or a Lo fire stage on a single
boiler. Since this is an isolated contact, it may switch a voltage between 24 V (ac) and
230 V (ac).

Mode 2 - One Modulating Boiler and Pump

The Relay 1 terminals (11 and 12) are isolated outputs in the control. There is no
power available on these terminals from the control. These terminals are to be used as
a switch to enable the modulating boiler to operate at Lo fire. Since this is an isolated
contact, it may switch a voltage between 24 V (ac) and 230 V (ac).

Relay 2 / P2 Contact

Mode 1 - Two ON / OFF Stages

The Relay 2 / P2 terminals (13 and 14) are isolated output in the control. There is no
power available on these terminals from the control. These terminals are to be used
as a switch to either make or break power to a boiler or a Hi fire stage on a single
boiler. Since this is an isolated contact, it may switch a voltage between 24 V (ac) and
230 V (ac).

Mode 2 - One Modulating Boiler and Pump

The Relay 2 / P2 terminals (13 and 14) are isolated output in the control. There is no
power available on these terminals from the control. These terminals are to be used
as a switch to either make or break power to a boiler pump. Since this is an isolated
contact, it may switch a voltage between 24 V (ac) and 230 V (ac).

Modulation Output

The Modulation Output Mod 1 terminals (15 and 16) provide a 4 to 20 mA or a 0 to 20 mA
output to the boiler. The modulating outputs replace any mechanical operator such as a
T991. Observe polarity when connecting the control to the boiler.

The 4 to 20 mA output can be converted to 2 to 10 V (dc) using an external 500 Ω resistor
across the Modulation Output terminals (15 and 16).

The 4 to 20 mA output can be converted to 1 to 5 V (dc) using an external 250 Ω resistor
across the Modulation Output terminals (15 and 16).

Relay

12

11

1

1

Relay

14

13

2 / P2

14

13

115 V (ac)

L

N

Relay

2 / P2

Connection to Operate

a 4 - 20 mA Device

15

+

16

Mod 1 mA

+

4-20 mA

Actuating Motor

6

+

7

Mod 1 mA

500 Ω resistor

4 - 20 mA converted

to 2 - 10 V (dc) output

OR

250 Ω resistor

4 - 20 mA converted
to 1 - 5 V (dc) output

Converting the 4 - 20 mA

Output to Operate a

1 - 5 or 2 - 10 V (dc) Device

+

1-5 or 2-10 V (dc)

Actuating Motor