beautypg.com

Powers 430/1430 Series HydroGuard Multi-Valve Hi/Lo Systems User Manual

Description, Operation, Application

background image

DESCRIPTION

The Powers 430 Hi/Lo Supply Fixture is a pre-piped system
consisting of two thermostatic valves and a PRV, designed
to provide consistent temperature control over a wide range
of flow requirements.

The unit includes: A Powers Series 430 thermostatic mixing
valve, a Powers Series 420 or 427 thermostatic mixing valve,
a Pressure Reducing Valve (PRV), pressure gauges, union
inlet strainer checkstops, dial thermometer, shut-off ball
valve, and interconnecting piping.

All components are pre-assembled for easy installation. The
stainless steel or durable white baked enamel steel cabinets
are designed for recessed or wall mount installation and pro-
vide protected access to the system.

OPERATION

This two valve supply fixture has a low capacity valve
that works in parallel with a high capacity valve.
During low demand, the low capacity valve will han-
dle the load requirements. As the load demand is
increased, the pressure reducing valve, which is set
at a certain pressure differential, will open and allow
flow through the high capacity valve to assist the low
capacity valve in meeting the load requirements.

APPLICATION

This is a typical application of the Hi/Lo Supply
Fixture for recirculation. Basic guidelines for
recirculating are provided below. Following
these guidelines will ensure stable
control of the domestic water
system during normal and
low/no use periods. Improper
piping causes the recirculat-
ing system to have erratic
pressure and temperature
fluctuations.

For Capacity requirements,
Refer to Form #MV430-3.5 or
the Hi/Lo Supply Fixture Brochure.

DO NOT recirculate low temperature hot water (LTHW)
and high temperature hot water (HTHW) with one pump;
return water may come back hotter than mixer set point.

To minimize natural heat convection, locate master
mixer below hot water source, or install mixer with heat
trap (a two-foot drop in the pipe line) as shown.

Do use two (2) circulating pumps. Use check valves to
prevent reverse flow.

Always use an Aquastat set at a temperature below set
point of mixer.

Be certain HTHW cannot be introduced into cold side of
mixer.

Always tie LTHW return to cold water side of mixing
valve, as well as back to hot water source.

WARNING

DO NOT OMIT THE LTHW CONNECTIONS; scalding and
severe personal injury may result from return supply
temperatures approaching hot water heater tempera-
tures.

A Watts Industries Co.

WATER

HEATER

STEAM

INPUT

PRV

HTHW

HTHW RETURN

CW

HEAT TRAP

LTHW

RETURN

LTHW

AQUASTAT

PUMP

Hi

AQUASTAT

PUMP

S u p p l y P r e s s u r e

G a u g e

O u t l e t P r e s s u r e

G a u g e

B a l l V a l v e

B a l l V a l v e

C h e c k s t o p s

C h e c k s t o p s

Lo

EXPANSION

TANK

S e n s o r

S h o c k A b s o r b e r

S o l e n o i d V a l v e

( O p t i o n a l )

2

qua

entry

AS

uality…Our Commitment

Q

qua

entry

AS

SERIES 460 ALARM

°

F

.

TEST

Set

Reset

TECHNICAL INSTRUCTIONS

HI/LO SUPPLY FIXTURE SYSTEM

Operation, Testing, Maintenance

TI430-420