beautypg.com

Warning, Warranty, Preventative maintenance – Powers SH1430 2 Valve HiLo & DV User Manual

Page 4

background image

USA:  Phone: 1.800.669.5430 • Fax 1.847. 229.0526 • www.powerscontrols.com

Canada:  Phone: 1.888.208.8927 • Fax 1.888.479.2887 • www.powerscontrols.ca

IS-P-SF-SH1430-2V-HiLo 1336

EDP# 6512306

© 2013 Powers

Warranty

n

The Seller warrants that the equipment manufactured by it and covered by this order or contract is free from defects in material and workmanship and, without

charge, equipment found to be defective in material or workmanship will be repaired, or at Seller’s option replaced F.O.B. original point of shipment, if written

notice of failure is received by Seller within one (1) year after date of shipment (unless specifically noted elsewhere), provided said equipment has been properly

installed, operated in accordance with the Seller’s instructions, and provided such defects are not due to abuse or decomposition by chemical or galvanic action.

ThiS expreSS warranTy iS in lieu OF and excludeS all OTher warranTieS, guaranTeeS, Or repreSenTaTiOnS, expreSS OF implied. There are

nO implied warranTieS OF merchanTaBiliTy Or OF FiTneSS FOr a parTicular purpOSe. The Seller assumes no responsibility for repairs made on the

Seller’s equipment unless done by the Seller’s authorized personnel, or by written authority from the Seller. The Seller makes no guarantee with respect to material

not manufactured by it.

A Watts Water Technologies Company

WARNING: This product contains chemicals known to the

State of California to cause cancer and birth defects or

other reproductive harm.

For more information: www.watts.com/prop65

Thermostatic water mixing valves are control devices which

must be cleaned and maintained on a regular basis.
1. Before servicing checkstops or piping, turn off the water

upstream. At least every twelve (12) months open up the

checkstops and check for the free movement of the poppet.

2. Before servicing the valve, turn off the water supply

upstream or close the checkstops. To close the checkstops,

turn the adjusting screw clockwise.

3. When opening checkstops after servicing, turn adjusting

screw counterclockwise to fully open position then turn

adjusting screw 1/2 turn clockwise for final setting.

4. Every three (3) months, check the maximum temperature

adjustments.

5. Every twelve (12) months, remove the valve bonnets and

check the internal components for freedom of movement.

Preventative Maintenance

n

See enclosed IS-P-LFMM430 and IS-P-LFSH1430.

Parts Kits

n

WARNING

!

Any changes in supply condition could effect the out-

let water temperature. Check and adjust the valves

accordingly to prevent injury to the users. After com-

pleting repairs, check discharge temperature, (105°F

[41°C]). Reset if necessary. Failure to perform this

operation could result in unsafe discharge tempera-

ture, which may cause injury or death.

This manual is related to the following products: