Powers MM430 Master Tempering Valves User Manual
Page 2

1. Installation should be in accordance with acceptable plumb-
ing practices. Flush all piping thoroughly before installation.
Installation and field adjustment are the responsibility of the
installer.
2. Valves are to be installed as close to building inlet supply as pos-
sible to prevent/minimize pressure fluctuations.
3. Valve body can be rotated to install in multiple position due to
union inlets (see Figure 2). Make sure that union nuts are tight-
ened securely.
4. Connect inlets and outlet and check for leaks.
5. When the Hydroguard supplies tempered water to self-closing
and/or solenoid valves, provide a shock absorber (Powers Part
No. 460-353) on the discharge line.
6. Before use, check discharge temperature. Reset if nec-
essary.
Operation Check:
After Hydroguard is installed, make certain the supply stop valves
and strainers are free and clean and ready for operation by disas-
sembling checkstops as shown in servicing.
Typical Flow
Hot and cold water supplies enter Hydroguard at indicated ports,
(see Figure 1) then flow past their respective balanced poppet plug
and seats. Next, hot and cold water flow is directed to the mixing
chamber where the thermostatic actuator is located.
Temperature adjustment screw moves the actuator to determine the
discharge temperature.
With a rise in discharge temperature due to pressure or tempera-
ture fluctuation on the inlet, the actuator expands, decreasing flow
of hot water. The reverse occurs with a drop in discharge
temperature.
• Cold water supply failure – causes actuator to expand allowing
the motor to drastically reduce hot water flow.
*
• Hot water supply pressure failure – causes actuator to contract
allowing return spring to close cold water port
*
.
*
When tested in accordance to conditions described in ASSE 1017.
Installation Instructions
n
Operation
n
Figure 2
Back Outlet
Front Outlet
Top Outlet
2
Figure 1
Temperature Adjustment Screw
Temperature Adjustment Locknut
Actuator
Mixing Chamber
Cold Water Seat
Hot Water
Seat
Cold Water
Hot Water
Plunger
Table 1, Capacity Tables, present the Hydroguard discharge capacity in gpm and l/m for various pressure differentials (the difference
between the lowest inlet pressure and the discharge pressure at the Hydroguard).
Capacity
n
* Minimum flow when Hydroguard is installed at or near hot water source with recirculated tempered water with continuously operating recirculating pump.
Flow Capacity at 50-50 mixed ratio
P r e s s u r e D r o p A c r o s s V a l v e
Model
Min.
Min. Flow
5psi
10psi
20psi
30psi
45psi
60psi
70psi
Flow Rate*
to ASSE 1017
C
V
(34 kPa)
(69 kPa)
(138 kPa)
(207 kPa)
(310 kPa)
(414 kPa) (517 kPa)
LFMM431
0.5 gpm
3 gpm
6.32
14 gpm
20 gpm
28 gpm
35 gpm
42 gpm
49 gpm
53 gpm
1.89 lpm
11 lpm
53 lpm
76 lpm
106 lpm
132 lpm
159 lpm
185 lpm
201 lpm
LFMM432
0.5 gpm
4 gpm
9.49
21 gpm
30 gpm
42 gpm
52 gpm
64 gpm
74 gpm
79 gpm
1.89 lpm
15 lpm
80 lpm
114 lpm
159 lpm
197 lpm
242 lpm
280 lpm
299 lpm
LFMM433
0.5 gpm
5 gpm
16.44
37 gpm
52 gpm
74 gpm
90 gpm
110 gpm
127 gpm 138 gpm
1.89 lpm
19 lpm
140 lpm
197 lpm
280 lpm
341 lpm
416 lpm
481 lpm
522 lpm
LFMM434
0.5 gpm
7 gpm
21.50
48 gpm
68 gpm
96 gpm
118 gpm
144 gpm
167 gpm
180 gpm
1.89 lpm
26 lpm
182 lpm
257 lpm
363 lpm
447 lpm
545 lpm
632 lpm
681 lpm
LFMM435
0.5 gpm
10 gpm
31.00
69 gpm
98 gpm
139 gpm
170 gpm
208 gpm
240 gpm
259 gpm
1.89 lpm
38 lpm
261 lpm
371 lpm
526 lpm
644 lpm
787 lpm
908 lpm
980 lpm
NOTICE
CAUTION
!