Working Area

The

Pr.07 program allows you to add a distance range that exceeds the tank’s height, thus enabling accurate readings of

complicated tank shapes with conic bottoms. This may be required when the vessel has a conical shape which is causing
false echoes and faulty measurements.

The minimum value is the Tank Height; the maximum value is 2X Tank Height. However this value cannot exceed the
maximum measurement range (16.41 ft. or 49.22 ft depending on the setting of

Pr.23)

Press / Action

Display

Description

and

simultaneously

Enter the Program Menu




Six Times

Cycle to Program #7




Displayed when entering the program

For Example:

Displays the last entered value or the Tank
Height (default)




and

Change the display to the desired value. The
minimum value is the Tank Height; the
maximum value is 2X Tank Height. However
this value cannot exceed the maximum
measurement range (16.41 ft. or 49.22 ft
depending on the setting of

Pr.23)

Saves the entered value.


Returns to

Pr.07

Selecting Level or Distance for the Display

The

Pr.08 program enables you to choose whether the SmartSonic display shows either distance or level measurements.

The setting of

Pr.08 does not affect the measurement selected in Pr.04, for the 4-20mA output. The two settings are:

d000: Distance mode (default): In this mode, the SmartSonic displays the distance from the sensor to the surface
of the process fluid

L000: Level mode: In this mode, the SmartSonic displays the level from the bottom of the tank.

Press / Action

Display

Description

and

simultaneously

Enter the Program Menu




Seven Times

Cycle to Program #8