Working Area
The
Pr.07 program allows you to add a distance range that exceeds the tank’s height, thus enabling accurate readings of
complicated tank shapes with conic bottoms. This may be required when the vessel has a conical shape which is causing
false echoes and faulty measurements.
The minimum value is the Tank Height; the maximum value is 2X Tank Height. However this value cannot exceed the
maximum measurement range (16.41 ft. or 49.22 ft depending on the setting of
Pr.23)
Press / Action
Display
Description
and
simultaneously
Enter the Program Menu
Six Times
Cycle to Program #7
Displayed when entering the program
For Example:
Displays the last entered value or the Tank
Height (default)
and
Change the display to the desired value. The
minimum value is the Tank Height; the
maximum value is 2X Tank Height. However
this value cannot exceed the maximum
measurement range (16.41 ft. or 49.22 ft
depending on the setting of
Pr.23)
Saves the entered value.
Returns to
Pr.07
Selecting Level or Distance for the Display
The
Pr.08 program enables you to choose whether the SmartSonic display shows either distance or level measurements.
The setting of
Pr.08 does not affect the measurement selected in Pr.04, for the 4-20mA output. The two settings are:
•
d000: Distance mode (default): In this mode, the SmartSonic displays the distance from the sensor to the surface
of the process fluid
•
L000: Level mode: In this mode, the SmartSonic displays the level from the bottom of the tank.
Press / Action
Display
Description
and
simultaneously
Enter the Program Menu
Seven Times
Cycle to Program #8