Kenco Engineering SmartSonic Transmitter (Integral) User Manual

Page 17

background image

Page 17




and

For Example:

Change the value to represent the desired 4mA
Point in either: Level, Distance, or Flow units.

To save the new value, press ENT. when the
far right digit (4mA value) is flashing. Returns
to

Pr.04

OR


To return to the main menu without saving,
press ESC. when the far left digit (4mA value)
is flashing. Returns to

Pr.04


NOTES:

The values for 4mA and 20mA must be different; otherwise an

Err error message is displayed.

The values for 4mA and 20mA should not be greater than the value used for the tank height (

Pr02). Because of

the dead-zone, the distance between the sensor and the surface of the target at its highest level should be a
minimum of 0.8 ft for Short-Range models, or 1.96 ft for Standard-Range models. These values can be greater if
you increased the Dead Zone (see Special Functions of

Pr.02).

After accessing the

Pr04 function, the unit generates a fixed current of 22mA on the 4-20mA line. When the

SmartSonic reverts to regular scanning mode, the 4-20mA line returns to regular functioning.

The default measurement for 4mA and 20mA in Level SmartSonic models is level.

The default measurement for 4mA and 20mA in Flow SmartSonic models is flow.

When changing from one measurement mode to another, the measurement units will be changed automatically
(for example, when changing from level mode to flow mode, the units will change from feet to GPM.)

The measurement mode selected for the 4-20mA values will not influence the measurement mode selected for
the display (

Pr.08).

In case of power reset, measurement configuration (level, distance, flow) will be saved according to the unit's last
configuration.

Configuring the 20mA Point

The

Pr.05 program enables you to set the location of the 20mA Point.

Press / Action

Display

Description

and

simultaneously

Enter the Program Menu




Four Times

Cycle to Program #5




Indicates that you are about to change the
20mA Point

For Example:

Displays either the last entered, or default
value.