Setting motion sensor sensitivity – CommScope Redwood version 3.2 User Manual
Page 27
Commissioning and Administration User Guide
24
To calibrate a Fixture:
1. In the Location Editor tab, select a Location. You can calibrate only one Location at a time.
2. Click the Calibrate Fixtures button. The process takes about 10 minutes.
The lights fully turn on for about 2 minutes so that the Sensors can assess the maximum
light reading. The lights then turn off to establish a zero-light level reading. Finally, the
Fixtures step through light levels in 10% increments.
3. Wait for calibration to complete before making any other changes. The lights return to
their existing Policy levels and the Calibrating progress box goes away.
IMPORTANT NOTE
•
;755/-)#.!*$#'05$)'+-!'%!59+5,/1!+-!$!%'-(#/!:+*$)'+-!+-#.=!97)75/!%+9)>$5/!?/5%'+-%!
,$.!/-$0#/!.+7!)+!*$#'05$)/!,7#)'<#/!:+*$)'+-%!%',7#)$-/+7%#.2!
•
3&/5/!'%!$!>$.!)+!1+!,7#)'<#/!:+*$)'+-%!>')&!)&/!*755/-)!?/5%'+-!+9!)&/!%+9)>$5/@!07)!)&'%!
5/67'5/%!)/,<+5$5'#.!,+?'-(!"'A)75/%!95+,!)&/'5!*755/-)!:+*$)'+-!'-)+ $!*+,,+-!
:+*$)'+-!$-1!)&/-!*$#'05$)'-(!)&$)!:+*$)'+-2!B+'-(!%+!%/1%!7
%')/@!07)!')!$%%7,/%!)&$)!.+7!&$?/!-$,/1!)&/!"'A)75/%!)+!5/9#/*)!)&/!:+*$)'+-@!+5!.+78##!
&$?/!)+!(+!)&5+7(&!)&/!"'A)75/!%+5)'-(!$($'-2!
•
B+!-+)!,$C/!$-.!+)&/5!*&$-(/%!)+!)&/!%')/!>&'#/!*$#'05$)'-(@!$%!)&'%!>'##!-/($)'?/#.!$99/*)!
)&/!*+-9'(75$)'+-!9'#/2!
Setting Motion Sensor Sensitivity
You can disable the motion Sensor or set the sensitivity level. Disabling the Sensor causes
the Fixture’s Location to ignore the Sensor’s motion data.
To set or change a Fixture motion Sensor sensitivity:
4. In the Maintenance tab, click the Location on the left and select the Fixture in the middle
pane.
5. From the drop-down menu, select Configuration.
6. The Sensor model is listed under Sensor Type.
7. Under Sensitivity, select the sensitivity level from the drop-down menu. The Sensor type
determines the sensitivity levels presented.
8. Click Apply.