beautypg.com

Interlock operation, Manual shut down, Interlock operation manual shut down – Bird Technologies DA40 UHF Series-Manual User Manual

Page 32

background image

Bird Technologies

18

4. Turn the interlock supply on at the transmitter.

5. Apply RF power to the load.

Interlock Operation
The overtemperature interlock is set for proper operation at the maxi-

mum rated ambient temperature of 45°C (113°F). The normally closed

switch opens at 86°C ± 5°C (186.8°F ± 9°F) and closes at 65°C ± 3°C

(149°F ± 5.4°F). This interlock is not dependent on AC line power.

Note:

The power interlock is set for proper operation when

the load is connected to AC power, the power switch is on, and
the circuit breakers are not tripped.

Manual Shut Down
When operation of the load has been completed, follow these steps for

shut down.

1. Turn the RF power to the load off.
2. Wait about 10 minutes to allow the air circulation to cool the resis-

tive elements inside the load to ambient temperature.

Note:

This cooling period will prevent unnecessary heat

stress on the resistors.

3. Turn off the AC power.
4. Disconnect the RF line.

CAUTION

Applying more than the rated average RF power to

the load may damage the load resistors.

WARNING

Do not operate above the rated capacity. See

“Specifications” on page 27 if unsure of the rating

the model load. The unit will handle a small

percentage of overload for brief periods of time

during transmitter tuning or adjustment. However,

long periods of overload (> 10% of rated power for >

30 min.) may damage the unit or cause the

temperature interlock to open.

CAUTION

Do not disconnect AC line power before turning off

RF power to the load. Application of full RF power to

the load while the fans are unpowered will cause the

load to overheat and destroy the resistor elements.