Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual
Page 59
Publication GMSI10-UM004B-EN-P - May 2010
Configuration Parameters 51
Name (XM Serial Configuration
Utility only)
A descriptive name to identify the alarm in the XM
Serial Configuration Utility.
Maximum 18 characters
Note: This parameter is not applicable
for Locked Rotor alarms.
Enable
Enable/disable the selected alarm.
Note: The Alarm Status is set to "Disarm" when the
alarm is disabled.
Condition
Controls when the alarm should trigger.
•
Greater than - Triggers the alarm when the
measurement value is greater than or equal to the
Alert and Danger Threshold values.
The Danger Threshold value must be greater than
or equal to the Alert Threshold value for the trigger
to occur.
•
Less than - Triggers the alarm when the
measurement value is less than or equal to the
Alert and Danger Threshold values.
The Danger Threshold value must be less than or
equal to the Alert Threshold value for the trigger to
occur.
•
Inside range - Triggers the alarm when the
measurement value is equal to or inside the range
of the Alert and Danger Threshold values.
The Danger Threshold (High) value must be less
than or equal to the Alert Threshold (High) value
AND the Danger Threshold (Low) value must be
greater than or equal to the Alert Threshold (Low)
value for the trigger to occur.
•
Outside range - Triggers the alarm when the
measurement value is equal to or outside the
range of the Alert and Danger Threshold values.
The Danger Threshold (High) value must be greater
than or equal to the Alert Threshold (High) value,
AND the Danger Threshold (Low) value must be
less than or equal to the Alert Threshold (Low)
value for the trigger to occur.
Options: Greater Than
Less Than
Inside Range
Outside Range
Note: This parameter is not applicable
for Locked Rotor alarms.
Alarm Parameters
Parameter Name
Description
Values/Comments
XM Configuration
Utility
EDS File
Check to Enable
Enabled
Clear to Disable
Disabled