Safe torque-off wiring requirements – Rockwell Automation 2099-BMxx-S Kinetix Safe Torque-off Feature Safety Reference Manual User Manual
Page 22
22
Rockwell Automation Publication GMC-RM002F-EN-P - June 2013
Chapter 3 Wiring Your Kinetix Safe Torque-off Drive
Safe Torque-off Wiring
Requirements
These are the safe torque-off (STO) wiring requirements. Wire should be copper
with 75
°C (167 °F) minimum rating.
Table 7 - Safe Torque-off (STO) Connector
beginning on
page 31
for Kinetix 6000 and Kinetix 7000
interconnect diagrams with other Allen-Bradley safety products.
IMPORTANT
The National Electrical Code and local electrical codes take precedence over the
values and methods provided.
Safe Torque-off (STO) Connector
Recommended Wire Size
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
Pin
Signal
Stranded Wire
with Ferrule
mm
2
(AWG)
Solid Wire
mm
2
(AWG)
STO-1
STO-2
STO-3
STO-4
STO-5
STO-6
STO-7
STO-8
STO-9
FDBK2+
FDBK2-
FDBK1+
FDBK1-
SAFETY ENABLE2+
SAFETY ENABLE-
SAFETY ENABLE1+
24V +
24V_COM
0.75 (18)
1.5 (16)
7.0 (0.275)
0.235 (2.0)
IMPORTANT
IMPORTANT
To be sure of system performance, run wires and cables in the wireways as
established in the user manual for your drive.
page 8
for the appropriate publication.