Installing Regulator Board P/N 814.61.00 in 2 to 15 Amp and 24 to 30 Amp GV3000/SE Bookshelf Drives
10-1
C
HAPTER
10
Installing Regulator Board P/N 814.61.00
in 2 to 15 Amp and 24 to 30 Amp
GV3000/SE Bookshelf Drives
Use the procedure in this chapter to replace the Regulator board (P/N 814.61.00) in
the GV3000/SE drives listed in table 10.1.
!
ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, adjust, operate, and/or service this equipment. Read and
understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in
severe bodily injury or loss of life.
ATTENTION: The drive is at line voltage when connected to incoming
AC power. Disconnect, lock out, and tag all incoming power to the drive
before performing the following procedure. Failure to observe this
precaution could result in severe bodily injury or loss of life.
ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait five
minutes for the DC bus capacitors to discharge and then check the
voltage with a voltmeter to ensure the DC bus capacitors are discharged
before touching any internal components. Failure to observe this
precaution could result in severe bodily injury or loss of life.
Table 10.1 – Model Numbers for 2 to 15 Amp and 24 to 30 Amp Drives
2 to 15 Amp
24 to 30 Amp
31ER40xx
31ET40xx
240ER40xx
240ET40xx
38ER40xx
38ET40xx
300ER40xx
300ET40xx
55ER40xx
55ET40xx
85ER40xx
85ET40xx
126ER40xx
126ET40xx
150ER40xx
150ET40xx