Page 40

Installing Regulator Board P/N 0-56921-6xx in 15 to 25 HP and 25 to 60 HP @460 VAC Drives
6-1
C
HAPTER
6
Installing Regulator Board
P/N 0-56921-6xx in 15 to 25 HP and
25 to 60 HP @460 VAC Drives
Use the procedure in this chapter to replace the Regulator board (P/N 0-56921-6xx) in
the 15 to 25 HP and 25 to 60 HP@460VAC GV3000/SE drives listed in table 6.1.
Refer to figure 6.1 (15 to 25 HP) or figure 6.2 (25 to 60 HP) as you perform the
procedure.
!
ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, adjust, operate, and/or service this equipment. Read and
understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in
severe bodily injury or loss of life.
ATTENTION: The drive is at line voltage when connected to incoming
AC power. Disconnect, lock out, and tag all incoming power to the drive
before performing the following procedure. Failure to observe this
precaution could result in severe bodily injury or loss of life.
ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait five
minutes for the DC bus capacitors to discharge and then check the
voltage with a voltmeter to ensure the DC bus capacitors are discharged
before touching any internal components. Failure to observe this
precaution could result in severe bodily injury or loss of life.
Table 6.1 – Model Numbers for 15 to 25 HP and 25 to 60 HP @460 VAC Drives
15 to 25 HP
25 to 60 HP
15V41xx
15V42xx
25V41xx
25V42xx
20V41xx
20V42xx
30V41xx
30V42xx
25G41xx
25G42xx
40V41xx
40V42xx
50V41xx
50V42xx
60G41xx
60G42xx