9-2
GV3000/SE Drive Version 6 Regulator Board Installation Instructions
Important: Read and understand the warning labels on the outside of the drive
before proceeding.
Step 1.
Shut Down the Drive
Step 1.1. Disconnect, lock out, and tag all incoming power to the drive.
Step 1.2. Wait five minutes for the DC bus capacitors to discharge.
Important: Read and understand the warning labels on the inside of the drive before
proceeding.
Step 2.
Verify That the DC Bus Capacitors are Discharged
Step 2.1. Open the drive’s outer cabinet door.
Step 2.2. Lower the plastic terminal strip shield at the top of the drive.
Step 2.3. Use a voltmeter to verify that there is no voltage at the drive’s AC input
power terminals, R, S, and T.
Step 2.4. Replace the plastic terminal strip shield.
Step 2.5. Ensure that the DC bus capacitors are discharged. To check
DC bus potential:
a. Stand on a non-conductive surface and wear insulated gloves. (600V)
b. Use a voltmeter to check the DC bus potential at the voltmeter test points
on the Power Module Interface board. See figure 9.1.
Figure 9.1 – Regulator Board Location in 200 to 400 HP Dives
R E S E T
PR O GR AM
R EV ER SE
FO R WAR D
AU TO
JO G
R EM O TE
RU N NI NG
Pa sswo rd
TO R QU E
H z
R PM
Kw
AM P S
VO LTS
S T O P
S TA R T
ENT ER
GND
GND
DC–
DC+
DC–
DC+
W T1
W T2
V
RL1
W
W T3
R
S
T
SL 2
T
Wi
rin
g
T
ra
y
DANGER
U
POW ER C O NNECT IONS
FU LL SHIELD TABS IN AN D ROTATE SHIELD OUT
CON NECT U SIN G 36 0MC M T WO HO LE TER MINAL LU GS
TORQUE TO 325IN-L B
Option
Board
Regulator
Board
Keypad
Power Module
Interface Board
Side View
(Enlarged)
Front View