Starting Up the Drive for Vector Regulation
Step 9.3 Press the
£
key until U.009 is displayed.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
Step 9.4 Press the ENTER key to view the test result.
Step 9.5 Refer to the U.009 parameter description in chapter 4 for the
corresponding cause and corrective action.
Step 9.6 Once the cause of the fault has been corrected, repeat the self-tuning
procedure (Step 8).
ATTENTION: The subsequent steps require rotating parts and/or
electrical circuits to be exposed. Stay clear if the drive must be running, or
disconnect and lock out or tag power source if contact must be made.
Failure to observe this precaution could result in severe bodily injury or
loss of life.
Important: The stop input on the terminal strip is not active when the Control
Source parameter (P.000) is set to LOCL, as it is during this start-up
procedure. Use the STOP/RESET key if you need to stop the drive.
Step 10. Check Motor Rotation Direction
This step involves verifying the speed reference is set to minimum speed, starting
the drive, and checking that the motor rotates in the correct direction. It is
performed with the motor disconnected from the load.
!
Step 10.1 Press the PROGRAM key until the PROGRAM LED turns off.
The keypad/display will enter monitor mode.