Programming Reference
Fault Code
AIn
bYc
EC
HIL
HU
LU
nCL
OC
OCA
OCb
OH
OL
UbS
Description
4 to 20 mA analog input signal loss
DC bus charging bypass contactor
Earth current failure (ground fault)
High line voltage
High DC bus voltage
Low DC bus voltage
Network communications loss
Overcurrent steady state
Overcurrent while accelerating
Overcurrent during DC braking
Drive overtemperature
Electronic motor overload
Asymmetrical bus charge
P.043 Fault Auto Reset Attempts
(continued)
Table 4.5 lists the faults that can be auto reset:
Table 4.5 – Faults That Can Be Auto Reset
All other faults cannot be auto reset.
Note that the auto reset feature will be disabled during the vector self-tuning
operation and the V/Hz identification procedure.
P.044 Fault Auto Reset Time
This parameter
specifies the amount
of time the drive will
wait to attempt to
reset drive faults.
Parameter Range:
1 to 60 seconds
Default Setting:
8
Parameter Type:
Configurable
Refer also to parameters: P.043 Fault Auto Reset Attempts
After the drive has detected the fault and is counting down the auto-reset time
period, the display will flash the countdown period in seconds in the following
format:
"Ar30...Ar29...Ar28...........Ar01...Ar00"
If during this countdown, the user presses the keypad STOP/RESET key, or asserts
the fault reset from the selected control source, the auto-reset countdown will stop,
and all faults will be reset.