beautypg.com

P.044 fault auto reset time – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 123

background image

4-37

Programming Reference

Fault Code

AIn

bYc

EC

HIL

HU

LU

nCL

OC

OCA

OCb

OH

OL

UbS

Description

4 to 20 mA analog input signal loss

DC bus charging bypass contactor

Earth current failure (ground fault)

High line voltage

High DC bus voltage

Low DC bus voltage

Network communications loss

Overcurrent steady state

Overcurrent while accelerating

Overcurrent during DC braking

Drive overtemperature

Electronic motor overload

Asymmetrical bus charge

P.043 Fault Auto Reset Attempts

(continued)

Table 4.5 lists the faults that can be auto reset:

Table 4.5 – Faults That Can Be Auto Reset

All other faults cannot be auto reset.

Note that the auto reset feature will be disabled during the vector self-tuning
operation and the V/Hz identification procedure.

P.044 Fault Auto Reset Time

This parameter
specifies the amount
of time the drive will
wait to attempt to
reset drive faults.

Parameter Range:

1 to 60 seconds

Default Setting:

8

Parameter Type:

Configurable

Refer also to parameters: P.043 Fault Auto Reset Attempts

After the drive has detected the fault and is counting down the auto-reset time
period, the display will flash the countdown period in seconds in the following
format:

"Ar30...Ar29...Ar28...........Ar01...Ar00"

If during this countdown, the user presses the keypad STOP/RESET key, or asserts
the fault reset from the selected control source, the auto-reset countdown will stop,
and all faults will be reset.