2-11

Starting Up the Drive for Vector Regulation

Step 5.11 Press the

£

key to display P.003, Minimum Speed.

ATTENTION: The drive can operate at and maintain zero speed. The
user is responsible for ensuring safe conditions for operating personnel by
providing suitable guards, audible or visual alarms, or other devices to
indicate that the drive is operating or may operate at or near zero
speed. Failure to observe this precaution could result in severe bodily
injury or loss of life.

This parameter sets the minimum speed in
RPM.

!

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 5.12 Press the ENTER key to display the default setting of P.003.

This displays the default setting for Minimum
Speed, 150 RPM.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 5.13 Press the

£

key to increase minimum speed or the

¥

key to decrease

minimum speed.

The adjustment range is:

0 to the value set for P.004 (Maximum
Speed).

VALUE ENTERED: