GV3000/SE 230 VAC Drive, Software Reference Version 6.04

P.055 STOP/RESET Key Disable

This parameter
disables the
STOP/RESET key
except from the
selected control
source.

ATTENTION: When P.055 is set to ON, the STOP/RESET key is
functional only from the selected control source. As a safety
precaution, Reliance Electric recommends that an emergency stop
push button be located near the drive in an easily accessible location.
As a further safety precaution, the user should post a warning on the
drive to alert personnel that the STOP/RESET key is not functional.
Failure to observe this precaution could result in severe bodily injury or
loss of life.

Table 4.7 details whether the STOP/RESET key is active based on the selected
control source (P.000) and P.055.

Table 4.7 – STOP/1n P.000 and P.055

!

Control Source

(P.000 =)

Front panel (LOCL)

Terminal strip (rE)

Network/option board (OP)

OIM/CS3000 (SErL)

Front panel (LOCL)

Terminal strip (rE)

Network/option board (OP)

OIM/CS3000 (SErL)

P.055

OFF

OFF

OFF

OFF

ON

ON

ON

ON

Front Panel

STOP/RESET Key

Active

Active

Active

Active

Active

Inactive

Inactive

Inactive

OIM/CS3000

STOP/RESET Key

Active

Active

Active

Active

Inactive

Inactive

Inactive

Active

Parameter Range:

OFF = Enable the STOP/RESET key regardless of

the control source

ON = Disable the STOP/RESET key except from the

selected control source

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters: P.000 Control Source