P.055 stop/reset key disable – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual
Page 132
4-46
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
P.055 STOP/RESET Key Disable
This parameter
disables the
STOP/RESET key
except from the
selected control
source.
ATTENTION: When P.055 is set to ON, the STOP/RESET key is
functional only from the selected control source. As a safety
precaution, Reliance Electric recommends that an emergency stop
push button be located near the drive in an easily accessible location.
As a further safety precaution, the user should post a warning on the
drive to alert personnel that the STOP/RESET key is not functional.
Failure to observe this precaution could result in severe bodily injury or
loss of life.
Table 4.7 details whether the STOP/RESET key is active based on the selected
control source (P.000) and P.055.
Table 4.7 – STOP/1n P.000 and P.055
!
Control Source
(P.000 =)
Front panel (LOCL)
Terminal strip (rE)
Network/option board (OP)
OIM/CS3000 (SErL)
Front panel (LOCL)
Terminal strip (rE)
Network/option board (OP)
OIM/CS3000 (SErL)
P.055
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Front Panel
STOP/RESET Key
Active
Active
Active
Active
Active
Inactive
Inactive
Inactive
OIM/CS3000
STOP/RESET Key
Active
Active
Active
Active
Inactive
Inactive
Inactive
Active
Parameter Range:
OFF = Enable the STOP/RESET key regardless of
the control source
ON = Disable the STOP/RESET key except from the
selected control source
Default Setting:
OFF
Parameter Type:
Tunable
Refer also to parameters: P.000 Control Source