P.052 auto/man key disable – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual
Page 127
4-41
Programming Reference
Parameter Range:
OFF = Enable the AUTO/MAN key regardless of
control source
ON = Disable the AUTO/MAN key except from the
selected control source
Default Setting:
OFF
Parameter Type:
Tunable
Refer also to parameters: P.000 Control Source
P.053 Manual Reference Preset Enable
P.052 AUTO/MAN Key Disable
This parameter
disables the
AUTO/MAN key
except from the
selected control
source.
When this parameter is set to ON, the AUTO/MAN key is functional only from the
selected control source. This parameter can be used to protect against inadvertent
reference change when the drive is controlled from the terminal strip (P.000 = rE) or
the option port (P.000 = OP).
Table 4.6 details whether the AUTO/MAN key is active based on the selected
control source and P.052.
Table 4.6 – AUTO/MAN Key Status Based on P.000 and P.052
Control Source (P.000 =)
Front panel (LOCL)
Terminal strip (rE)
Network/option board (OP)
OIM/CS3000 (SErL)
Front panel (LOCL)
Terminal strip (rE)
Network/option board (OP)
OIM/CS3000 (SErL)
P.052
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Front Panel
AUTO/MAN Key
Active
Active
Active
Inactive
Active
Inactive
Inactive
Inactive
OIM/CS3000
AUTO/MAN Key
Inactive
Active
Active
Active
Inactive
Inactive
Inactive
Active