U.028 losses compensation gain, U.030 svc slip adjust – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual
Page 172
4-86
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
U.028 Losses Compensation Gain
This parameter
specifies the gain
applied to the speed
loop reference signal
to generate the
losses compensation
signal. The result is
added to the speed
PI output to produce
the torque reference
signal.
Parameter Range:
0.0 to 1.000
Default Setting:
0.0 (Disable losses compensation)
Parameter Type:
Tunable
Refer also to parameters: U.026 Current Compounding Gain
U.027 Inertia Compensation Gain
Losses compensation is the scaled output of the speed loop S/Ramp block (speed
reference). It is added to the speed loop output and the inertia compensation signal
to produce the final torque reference.
Refer to the speed loop block diagram in Appendix G.
U.030 SVC Slip Adjust
Parameter Range:
0.50 to 1.50
Default Setting:
1.00
Parameter Type:
Tunable
Refer also to parameters: N/A
For SVC operation, in the absence of a speed feedback device, operation of the
speed loop is based on an estimated speed feedback. Estimated speed feedback is
based on knowing the slip of the motor, which changes with motor temperature.
This parameter is provided to accommodate various operating conditions.
For a cold motor, the typical value should be 0.80. For a hot motor, the value
should be 1.0.
This parameter
adjusts the slip
compensation to
match the operating
temperature of the
motor.
This feature applies
to SVC operation
only.