Step 4. Program the Drive for Vector Regulation

This step describes how to change parameter P.048 (Volts/Hertz or Vector
Regulation) to vector.

Within vector regulation, you can program the drive for flux vector control (FVC) or
sensorless vector control (SVC). FVC operation requires an encoder. SVC
operation does not require an encoder. Both options require U.048 to be set to
UEC. In a later step, you will select either the FVC option or the SVC option.

When you enter the value for vector regulation (P.048 = UEC), the drive will
performs a diagnostic check. After the diagnostics, the drive enters monitor mode
with speed displayed.

Step 4.1 Press the

£

key until P.048, Volts/Hertz or Vector Regulation, is displayed.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 4.2 Press the ENTER key.

The default setting for P.048 is V/Hz
regulation.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 4.3 Press the

£

key to display UEC, vector regulation.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM