Appendix B Specifications
Communications Protocols
(Optional)
DeviceNet
ControlNet
Ethernet I/P
Lon Works
Dual-port Ethernet I/P
Can Open
Profibus
RS485 HVAC
Modbus
RS485 DF1
Interbus
RS232 DF1
USB
Enclosure
NEMA 1 (standard)
IP21 (IEC)
NEMA 12 (optional)
IP42 (IEC)
Lifting Device
Standard / Removable
Mounting Arrangement
Mounting Sill Channels
Structure Finish
Epoxy Powder – Paint
Exterior Sandtex Light Grey (RAL 7038) – Black (RAL 8022)
Internal – Control Sub Plates – High Gloss White (RAL 9003)
Interlocking
Key provision for customer input Disconnecting Device
Corrosion Protection
Unpainted Parts (Zinc Plated / Bronze Chromate)
Ambient Temperature
0…40 °C (32…104 °F) / 0…50 °C (32…122 °F) - optional
Fiber Optic Interface
Rectifier – Inverter – Cabinet (Warning / Trip)
Door Filter
Painted Defuser with Matted Filter Media
Door Filter Blockage
Air Flow Restriction Trip / Warning
Storage and Transportation
Temperature Range
-40…70 °C (-40…185 °F)
Relative Humidity
Max. 95%, non-condensing
Altitude (Standard)
0…1000 m (0…3300 ft)
Altitude (Optional)
1001…5000 m (0…16,400 ft)
Seismic (UBC Rating)
1, 2, 3, 4
Standards
NEMA, IEC, CSA, UL, ANSI, IEEE
(1) Voltage Sag tolerance is reduced to -25% when control power is supplied from medium voltage via CPT.
(2) MOVs are used for 18 Pulse. Surge arrestors are used for AFE/Direct-to-Drive configurations.
(3) Short-circuit fault rating based on input protection device (contactor or circuit breaker).
(4) BIL rating based on altitudes < 1000 m (3300 ft) Refer to factory for derating on altitudes >1000 m.
(5) Optional.
(6) Under certain conditions, power system analysis will be required.
Table 15 - General Design Specifications (Continued)
Description