F-4 Specifications
7000A-UM151D-EN-P – March 2013
7000 “A” Frame
Dimensions / Weights
Nominal Line
Voltage
Drive Type
VFD
Maximum
Current
Total Width
Approx. Weight
lb (kg)
Millimeters
Inches
2400V 60 Hz
or
3300V 50 Hz
or
4160V 50/60 Hz
Configuration #1 – Direct-to-Drive
140
2100
82.67
4300 (1955)
Configuration #2 – AFE Rectifier with separate isolation
transformer
160 2400
94.49
8300
(3765)
Configuration #3 – AFE Rectifier with Integral isolation
transformer
160 2400
94.49
9800
(4455)
6600V 50/60 Hz
Configuration #1 – Direct-to-Drive
93
2400
94.49
6500 (2955)
Configuration #2 – AFE Rectifier with separate isolation
transformer
105 2800
110.24
10000
(4545)
Configuration #3 – AFE Rectifier with integral isolation
transformer
105 2800
110.24
7500
(3410)
Note:
Total Depth = 1000 mm (39.37 in.)
Total Height without fan shroud = 2318 mm (91.25 in.)
Total Height with fan shroud = 2643 mm (104.05 in.)
Nominal Power Ratings
Nominal Line Voltage
VFD Current Range
(Amps)
Nominal HP Range
Nominal kW Range
2400V 60 Hz
46 – 160
200 – 700
150 – 522
3300V 50 Hz
46 – 160
250 – 1000
187 – 750
4160V 50/60 Hz
46 – 160
350 – 1250
260 – 933
6600V 50/60 Hz
40 – 105
500 - 1250
400 – 933