Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control (PanelView 550) User Manual
Page 210
E-10
Preventative Maintenance Schedule
7000A-UM151D-EN-P – March 2013
7000 “A” Frame
Rockwell Automation PowerFlex 7000 Preventative Maintenance Service Schedule
(cont.)
Interval
Period
(in
years)
11 12 13 14 15 16 17 18 19 20
Commissioning Activities
Air-Cooling
System
Door Mounted Air Filters
C/R C/R C/R C/R C/R C/R C/R C/R C/R C/R
Main
Cooling
Fan
Motor
I I I
RFB/R
I I I I I I
Redundant
Cooling
Fan
Motor
(if
supplied) I I I
RFB/R
I I I I I I
Small Aux. Cooling Fans “Caravel”
I
I
I
I
R
I
I
I
I
R
Liquid-Cooling
System
Mesh Filters
C C C C C C C C C C
De-ionizing Filter Cartridge
R R R R R R R R R R
All
Fittings/Connections/Hose
Clamps I I I I I I I I I I
Redundant
Cooling
Pump
Motors/Pumps I I I I I I I I I I
Redundant
Cooling
Pump
Motor
Seals I I I I I I I I I R
Thermostatic
Valve
Element
I I I R I I I I I I
Power Switching
Components
Power
Devices
(SGCTs/SCRs)
I R I I I I I I I I
Snubber
Resistors/Sharing
Resistors/HECS
I I I I I I I I I I
Rectifier Snubber Capacitors
I
I
I
I
I
I I I I
Rv/R
Inverter
Snubber
Capacitors
I I I I I I I I I R
Integrated Gate Driver Power Supply
I
I
I
I
RFB/R
I
I
I
I
RFB/R
Integral
Magnetics/Power
Filters
Isolation
Transformer/Line
Reactor
I I I I M I I I I M
DC
Link/Common
Mode
Choke
I I I I M I I I I M
Line/Motor
Filter
Capacitors
I I I I M I I I I M
Control Cabinet
Components
AC/DC
and
DC/DC
Power
Supplies
I I I I
RFB/R
I I I I
RFB/R
Control
Boards
I I I I I I I I I I
Batteries (DCBs and CIB)
I
R
I
I
R
I
I
R
I
I
Batteries (UPS)
I I I I R I I I I R
Connections
Low Voltage Terminal Connections/
Plug-in Connections
I I I I I I I I I I
Medium
Voltage
Connections
I I I I I I I I I I
Heatsink
Bolted
Connections
I I I I I I I I I I
Medium Voltage Connections (Rectifier)
–
I
–
–
–
I
–
–
–
I
Medium Voltage Connections (Inverter)
– – – – – – – – – I
Enhancements
Firmware
– Rv – – Rv – – Rv – –
Hardware
– Rv – – Rv – – Rv – –
Operational
Conditions
Parameters
I Rv I I Rv I I Rv I I
Variables
I Rv I I Rv I I Rv I I
Application
Concerns
I Rv I I Rv I I Rv I I
Spare Parts
Inventory/Needs
I Rv i I Rv I I Rv I I
Only applies to air-cooled VFDs (i.e. ‘A’ Frame and ‘B’ Frame)
If filter supplied is not a washable type, replace filter. If filter supplied is a washable type, wash or replace (depending on state of filter).
Only applies to liquid-cooled VFDs (i.e. ‘C’ Frame)
A 4-year replacement interval applies to 6-pulse or 18-pulse versions. Active Front End rectifiers have a 10-year rectifier snubber capacitor replacement interval.
Replace UPS batteries yearly for 50°C rated VFDs.
When rectifier snubber capacitors are replaced, the MV connections for rectifier need to be inspected.
When inverter snubber capacitors are replaced, the MV connections for inverter need to be inspected.
These components may be serviced while the VFD is running.