Component Definition and Maintenance 4-31

7000 “A” Frame

7000A-UM151D-EN-P – March 2013


Impeller Removal from Motor Shaft


The fan impeller is held onto the motor shaft with a split tapered bushing.
This bushing is positioned on the motor shaft and through the center of the
impeller. Two cap screws, when tightened to 10.2 N-m (7.5 ft-lbs.), lock
the bushing onto the motor shaft and the impeller to the bushing.

Safety

notes


The impeller is fragile. Do not allow the impeller to support the weight of
the motor.


If vertical, the impeller and bushing may fall when loosening cap screws.
Physical injury or component damage may result.

A

B

C

D

E

A – Taper surfaces

B – Capscrews

C – Split in Taper Bushing

D – Key

E – Threaded Hole for Separating Tapers

DO NOT LUBRICATE

CAPSCREWS, BORE,

OR BUSHING BARREL

Figure 4.23 – Cutaway View of Fan Impeller and Bushing

Impeller Maintenance
(DC Link / Fan Section)