4-50

Component Definition and Maintenance

7000A-UM151D-EN-P – March 2013

7000 “A” Frame



Interface Module (IFM)


The Interface Module is used to make all customer useable connections to
the ACB. The pin numbers listed on the following pages refer to IFM pin
numbers.

Even pin numbers

Odd pin numbers

Connection to ACB (J8)

Figure 4.39 – Interface Module



Analog Inputs and Outputs

The PowerFlex 7000 offers one isolated process current loop transmitter
and three isolated process current loop receivers, embedded into the
control. These are accessible on the ACB.

The isolated Process Output is configured as 4-20 mA. The three isolated
process inputs are individually configurable for either a range of -10/0/+10V
or 4-20 mA (Refer to Programming Manual).

The following information will show the connections for each input and
output.