beautypg.com

European union directive compliance, Hazardous locations – Rockwell Automation 6181X-12TPXPDC Industrial Integrated Computers for Hazardous Locations User Manual

Page 3

background image

Industrial Computers for Hazardous Locations 3

Rockwell Automation Publication 6181X-IN001C-EN-P - April 2011

European Union Directive Compliance

This product meets the European Union Directive requirements when installed within the
European Union or EEA regions and have the CE mark. A copy of the Declaration of
Conformity is available at the Rockwell Automation website

http://www.ab.com

under Product

Certification.

To comply with EN 55022 and EN 55024, use the following shielded or unshielded cable as
specified in this table.

Hazardous Locations

This equipment is suitable for these location categories.

ATTENTION: To comply with EN 55022 and EN 55024, all I/O cables
must be less than 30 m (98.42 ft). These cables must not exit the
building at any point and shall not directly connect to cables outside the
building.

Cable Type

Required Attribute

LAN

Shielded or Unshielded

USB

Shielded

Serial RS-232

Shielded

DVI

Shielded

VGA

Shielded

DC Power

Unshielded

Cat. No.

Region

Class/Division/Zone Rating

Temperature

6181X-NPXPDC,
Non-display

United
States

Class I Division 2, Groups A, B, C, D T4

-20 °C

≤ T

a

70 °C

(1)

(-4 °F < T

a

< 158 °F)

Class I Zone 2, IIC, T4

Canada

Class I Division 2, Groups A, B, C, D T4

Class I Zone 2, IIC, T4

Europe

ATEX II 3 GD, Ex nA IIC Gc, Ex tc IIIC Dc

6181X-12TPXPDC,
Display

United
States

Class I Division 2, Groups A, B, C, D T4

-20 °C

≤ T

a

≤ 55 °C

(-4 °F < T

a

< 131 °F) (Display side)

-20 °C

≤ T

a

≤ 70 °C

-4 °F < T

a

< 158 °F) (Backside)

(1)

(1)

The entire 6181X-NPXPDC computer and the backside of the 6181X-12TPXPDC display are required to be mounted in a
restricted access location.

Class I Zone 2, IIC, T4

Canada

Class I Division 2, Groups A, B, C, D T4

Class I Zone 2, IIC, T4

Europe

ATEX II 3 GD, Ex nA nC IIC T4 Gc,

Ex tc IIIC T135 Dc

This manual is related to the following products: