beautypg.com

Rockwell Automation 6181X-12TPXPDC Industrial Integrated Computers for Hazardous Locations User Manual

Page 14

background image

14 Industrial Computers for Hazardous Locations

Rockwell Automation Publication 6181X-IN001C-EN-P - April 2011

4.

Slide the mounting clips into the holes on the top, bottom, and sides of the computer.

5.

Gradually tighten the clips, one at a time, around the bezel by using the specified
sequence starting with the center clips and continuing to the corner clips.

6.

Tighten the mounting clips to a torque of 1.4 N•m (12 lb•in) by using the sequence in

step 5

, being sure not to overtighten.

Repeat this process at least three times until the clips are properly torqued, making sure
the gasket is compressed uniformly against the panel.

ATTENTION: Tighten the mounting clips to the specified torque to provide a
proper seal and prevent damage to the product. Rockwell Automation assumes
no responsibility for water or chemical damage to the product or other
equipment within the enclosure because of improper installation.

1

10

9

2

7

8

5

4

3

6

This manual is related to the following products: