Rockwell Automation 1779-KP3R DATA HIGHWAY II User Manual
Page 42

Programming
Chapter 3
3Ć7
See the section titled Programming Examples, at the end of this chapter,
for more command examples.
Syntax for the TMOVE Command With the FROM and NOSTATUS Qualifiers
The syntax for the TMOVE command when using the FROM and
NOSTATUS qualifiers is:
TMOVE FROM TO NOSTATUS or
TMOVE TO FROM NOSTATUS
Where:
is:
TMOVE
the command that tells the KP3 to transfer data to or from a remote
node.
FROM
the qualifier that specifies where you want to transfer data from;
you can abbreviate as F. FROM is always followed by an address
(which must include a data table address and can include a remote
node address).
the address where the data that you are moving resides. This is
either a Data Highway II node address or programmable controller
memory address (see section titled Addressing Techniques for
addressing style information).
TO
the qualifier that specifies the destination of the data transfer; you
can abbreviate as T. You must specify the TO qualifier and it must
be followed an address (which must include a data table address
and can include a remote node address).
the destination address for the data you are moving. This is either
a Data Highway II node address or programmable controller
memory address (see section titled Addressing Techniques for
addressing style information).
NOSTATUS
the qualifier used only with a TMOVE command designed to
transfer data to some remote node. Use when error reporting is not
necessary and you want to eliminate the time spent receiving
information about the success or failure of the command. You can
abbreviate as N.
These are examples of using the TMOVE command with the FROM and
NOSTATUS qualifiers:
TMOVE FROM :66$010 TO $B2:3 NOSTATUS
TM T $B2:3 F :66$010 N