4-8 Module Operation and System Considerations

Use the following equation to determine the decimal value for the
current output:

Use the following equation to determine the decimal value for the
voltage output:

Voltage Range

Decimal
Representation for
Output Word

Number of

Significant
Bits

Resolution per
LSB

-10 to +10V dc

- 1LSB

-32,768 to +32,764

14 bits

1.22070 mV

0 to +10V dc

- 1LSB

0 to +32,764

13 bits

0 to 5V dc

0 to +16,384

12 bits

1 to 5V dc

+3,277 to +16,384

11.67 bits

×

Desired Current Output (mA) = Output Decimal V alue

For example, if an output value of 4 mA is desired, the value to be put in the
corresponding word in the output image can be calculated as follows:

×

4 mA

=

6242

Note: The actual resolution for analog current outputs is 2.56348

µ

A per LSB,

where the LSB position in the output word is indicated as:

32,768

21 mA

32,768

21 mA

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

LSB

X

X

X

= Bit Not Used

×

Desired Voltage Output (V dc) = Output Decimal V alue

For example, if an output value of 1V dc is desired, the value to be put in the
corresponding word in the output image can be calculated as follows:

×

1V dc = 3277

Note: The actual resolution for analog voltage outputs is 1.22070 mV per LSB,
where the LSB position in the output word is indicated as:

32,768

10V dc

32,768

10V dc

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

LSB

X

X

X

= Bit Not Used