Publication 1747-RM623D-EN-P - June 2006
Prepare to Use the ControlNet Scanner 2-7
Module Status (M1:e.1)
See Troubleshooting for probable causes and recommended actions.
ControlNet Status (M1:e.2)
See the table that contains bit numbers and their descriptions.
Value
Description
0x20
The scanner is not configured.
0x21
The current configuration is not valid.
0x22
Connections are configured, but no connections are established.
0x23
Connections are configured, but only 25% are successfully established.
0x24
Connections are configured, but only 50% are successfully established.
0x25
Connections are configured, but only 75% are successfully established.
0x26
All configured connections are established.
0x42
The node address is set to 00. This caused the scanner to erase network and
connection configuration stored in flash.
0x43
The scanner detected a network error due to a ControlNet cable problem or there
are no other nodes on the network.
0x44
The scanner has the same ControlNet address as another device on the network.
Bit 0-2
Channel A status
Value
LED State
000
Off
001
Green
010
Flashing green/off
011
Flashing red/off
100
Flashing red/green
101
Alternating red/off
110
Alternating red/green
111
Red
Bit 3
Reserved
Bit 4-6
Channel B status
Value
LED State
000
Off
001
Green
010
Flashing green/off
011
Flashing red/off
100
Flashing red/green
101
Alternating red/off
110
Alternating red/green
111
Red
Bit 7-15
Reserved