beautypg.com

Installation chapter 2 – Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual

Page 28

background image

Installation

Chapter 2

2Ć16

Figure 2.9

Connection to Allen-Bradley 1775-KA Module

1

2

7

3

25

4

5

6

8

20

1

3

25

2

7

4

5

6

8

20

Connect the Shield at One End Only

RS–232–C
CHANNEL
Connector
of 1775–KA
Module

RS–232–C
CHANNEL
Connector
of 1771–KA

Conductors 2 and 7, 3 and 25 must be twisted pairs for distances longer
than 50 feet.

Set switch 3 (on the 1775–KA) OFF when the module is communicating
with another Allen-Bradley device.

10010–I

1

2

1

2

Module

If you want to connect the 1775–KA module to a modem or computer, use
the cabling pinout diagram (Figure 2.10) to construct your own cable.