Remote Error Codes Received from the
1773-KA Module
Appendix B
BĆ10
Error
Error
Code
Type
Meaning
169
local
Either the number or the expression following the
'/' in an address has a value outside the range 0 to
15 (decimal).
171
local
Value specified in a bit assignment statement was
other than a zero or a one.
177
local
Illegal use of EXIT command.
178
local
Illegal use of STOP command.
179
local
STOP encountered in procedure.
188
local
Attempt to read/write at bad address.
189
local
Unable to evaluate the expression in the given base.
This will occur, for example, if the argument of a
FROM BCD function is not a valid BCD bit
pattern. It will also occur when invalid characters
occur in numeric values (e.g., 57 + 12X").
192
local
Function being used is not defined.
194
local
Expression is too complex.
199
local
Attempt to divide by zero.
200
local
Bad port specifier. That is, the character following
the '#' is other than 'H', 'h', 'M', or 'm'.
201
local
User symbol used as part of remote address
specification.
202
local
Undefined data following assignment command.
This error would occur, for instance, if the modifier
UNRPOT were used instead of UNPROT.
203
local
Error in remote specification.
1.A character other than '@' or 'following the
station number specification (...=#H045*T...).
2.Something other than EOL, PROT, or UNPROT
following a remote source address
(...=#H012$S5:8 + 9).
204
local
Third-party transfer. That is, in an assignment
command, both the source and the destination were
remote addresses.
205
local
Error in evaluating a PLC-2 address, or PLC-2
address greater than 65,535.
206
local
Zero range specified in an assignment command.