Rockwell Automation 1775-KA PLC-3 Communication Adapter Module User Manual User Manual
Page 204

Remote Error Codes Received from the
1773-KA Module
Appendix B
BĆ12
Error
Error
Code
Type
Meaning
231
reply
For all PLC-3 read and write commands:
There is an error in converting the block address
(major section>63, context >15, or section >15).
232
reply
For all PLC-3 read and write commands:
Three or fewer addressing levels specified in for a PLC-3
word address.
233
reply
For all PLC-3 read and write commands:
Conversion of a file address to a block address
resulted in more than 9 addressing levels.
234
reply
For all PLC-3 red and write commands:
Symbolic address not found.
235
reply
For all PLC-3 red and write commands:
Symbolic address is of length zero or is longer than
8 bytes.
236
reply
For PLC-3 read commands:
1.File not found.
2.Destination address does not have enough levels
to specify a PLC-3 word (for word-range reads)
or a file (for file reads).
3.The PLC-3 address specifies more levels than
required.
4.Word specified by the PLC-3 address does not
exist.
For PLC-3 bit write commands:
1.File not found.
2.Destination address does not specify a PLC-3
word.
3.The PLC-3 address specifies more levels than
required.
4.Word specified by the PLC-3 address does not
exist.
For other PLC-3 write commands:
1.Destination file not found.
2.Destination address does not point to a word (for
word-writes) or a file (for file writes).
3.Destination address specifies more levels than
required.