Specifications
1784-PCC Communication Card
PCMCIA Type
Type II form-factor network adapter card
PCMCIA Standard
Compliant to PCMCIA Standard, release 2.1
Power Requirements
5V dc @ 225 mA maximum Class 2
Conductor
Category 2
1
Operating Temperature
2
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 50°C (32 to 122°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
-40 to 85° C (-40 to 185° F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5-95% non-condensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz
Shock
IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g
Emissions
CISPR 11:
Group 1, Class A
Radiated RF Immunity
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
Certifications:
(when product is marked)
UR UL Recognized Component Industrial Control Equipment
CE
3
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
3
Australian Radiocommunications Act, compliant with:
AS/NZS 2064; Industrial Emissions
1784-PCC1 Cable Specifications
Total length of cable