A-4 Specifications

Max. Capacitive Load
(Voltage Outputs)

1 µF

Overall Accuracy

(2)

at

25°C

Voltage Terminal: ±0.5% full scale
Current Terminal: ±0.5% full scale

Overall Accuracy at 0 to
60°C

Voltage Terminal: ±0.6% full scale
Current Terminal: ±1.0% full scale

Accuracy Drift with
Temperature

Voltage Terminal: ±0.01% full scale per °C
Current Terminal: ±0.01% full scale per °C

Output Ripple;

(3)

range 0 - 50 kHz
(referred to output range)

±0.05%

Non-linearity
(in percent full scale)

±0.4%

Repeatability

(4)

(in percent full scale)

±0.05%

Output Impedance

10

(nominal)

Open and Short-Circuit
Protection

Yes

Maximum Short-Circuit

Current: 40 mA

Maximum Open Circuit

Voltage: 15V

Output Response at
System Power Up and
Power Down

+2.0V dc to -1.0V dc spike for less than 6 ms

Rated Working Voltage

30V ac/30V dc

Channel Diagnostics

Over range by bit reporting

Output Group to
Backplane Isolation

500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced
insulation)

(1) The over-range flag will come on when the normal operating range is exceeded. The module will continue to

convert the analog output up to the maximum full scale range. The flag automatically resets when within the
normal operating range.

(2) Includes offset, gain, drift, non-linearity and repeatability error terms.
(3) Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(4) Repeatability is the ability of the output module to reproduce output readings when the same controller value is

applied to it consecutively, under the same conditions and in the same direction.