5-6 Module Diagnostics and Troubleshooting
Module Condition Errors
Common Hardware Errors
There are several general common hardware errors. The following
table lists these errors.
Hardware Specific Errors
If the module detects that any of the analog to digital converters are
not functioning properly, one of the following hardware errors is set:
Module Inhibit Function
Some controllers support the module inhibit function. See your
controller manual for details.
Whenever the combination module is inhibited, it enters the program
mode and the output channels are changed to the state configured for
the program mode. The input channels of the module continue to
provide information about changes at its inputs to the 1769 Compact
Bus Master (for example, a CompactLogix controller).
Table 5.3 Common Hardware Errors
Mod_Error
(11:9)
Extended_Error
_Info (8:0)
Error Description
0
000
No Errors
1
000
General hardware error; no additional
information
1
001
Power-up reset state
Table 5.4 Specific Hardware Errors
Mod_Error
(11:9)
Extended_Error
_Info (8:0)
Error Description
1
100
General H/W error (ASIC)
1
101
Microprocessor H/W error
1
102
SPARE (not part of 1769-IF4XOF2 design)
1
103
SPARE (not part of 1769-IF4XOF2 design)