Extended error codes -5, Extended error codes, Extended_error_info field – Rockwell Automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual
Page 65

Publication 1769-UM008A-EN-P - November 2001
Module Diagnostics and Troubleshooting 5-5
Extended_Error_Info Field
Check the Extended_Error_Info field when a non-zero value is in the
Mod_Error field. The following are some Extended_Error_Info error
codes:
Extended Error Codes
When invalid values are entered in the configuration file, the module
ignores the invalid configuration, generates a non-critical error, and
keeps operating with the previous configuration. The following table
explains the extended error codes for the 1769-IF4XOF2 analog
combination module:
Table 5.1 Extended Error Information Field
Error Type
Mod_Error (11:9)
Extended_Error_Info (8:0)
No Error
0
always 000
Hardware Error
1
000 = no additional information
001 = Power-up Reset
002 to 0FF = general common errors
100 to 1FF = module specific errors
Configuration Error
2
000 = no additional information
001 to 1FF = module specific errors
Table 5.2 Extended Error Codes
Error Type
Hex
Equivalent
(1)
Module
Error
Code
Bits (11:9)
Extended Error
Information
Code Bits 8:0
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No Error
General Common
Hardware Error
X200
001
0 0000 0000
General Hardware Error; no additional information
X201
001
0 0000 0001
Power-up reset state
Hardware-
Specific Error
X300
001
1 0000 0000
General hardware error (ASIC)
X301
001
1 0000 0001
Microprocessor hardware error
1769-IF4XOF2 Specific
Configuration Error
X400
010
0 0000 0000
General configuration error; no additional information
X401
010
0 0000 0001
invalid Fault Value Entered for (channel 0)
X402
010
0 0000 0010
invalid Fault Value Entered for (channel 1)
X403
010
0 0000 0011
invalid Program Value Entered for (channel 0)
X404
010
0 0000 0100
invalid Program Value Entered for (channel 1)
(1) X represents the “Don’t Care” digit.